Description:
|
Hazard: The exit door is blocked by tables.
|
Description:
|
Hazard: Oxygen and acetylene cylinders improperly stored.
|
Description:
|
Fire Extinguisher
|
|
Standard:
|
1910.37(f)(1)
|
Standard:
|
1910.253(b)(2)
|
Standard:
|
1926.150(a)(4)
|
|
Abatement:
|
Remove the tables or provide other means of acceptable egress and remove the exit sign.
|
Abatement:
|
Employer separated the cylinders by more than 20 feet.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Description:
|
Hazard: Materials stored too close to light fixtures creating a fire hazard.
|
Description:
|
Hazard: Work stations for garments were overcrowded and obstructed egress path in the vent of fire.
|
Description:
|
Hazard: Flammable liquids were not kept in covered containers when not actually in use.
|
|
Standard:
|
1910.176(c)
|
Standard:
|
1910.37(d)
|
Standard:
|
1910.106(e)(2)(iv)(A)
|
|
Abatement:
|
Materials were removed from top shelves to eliminate fire potential.
|
Abatement:
|
Employer began redesigning product flow lines to reduce buildup of product.
|
Abatement:
|
Properly store flammable liquid.
|