Description:
|
This photo does not document a violation. The employees are installing metal siding on housing units, working from pump jack scaffolds. The scaffolds are equipped with a guardrail and safety net system for fall protection. The employer does not have end rails up yet, but they are not at 10' in these photos.
|
Description:
|
This scaffold was within 10 feet of the overhead powerline with 300 volts to 50KV.
|
Description:
|
This scaffold was within 10 feet of the overhead powerline with 300 volts to 50KV.
|
|
Standard:
|
1926.452(j)(1-7)
|
Standard:
|
1926.451(f)(6)
|
Standard:
|
1926.451(f)(6)
|
|
|
|
Abatement:
|
The scaffold should not be erected, dismantlled, used or altered near energized powerlines.
|
Abatement:
|
The scaffold should not be erected, dismantlled, used or altered near energized powerlines.
|
|
|
|
|
|
|
|
|
|
|
|
|
Description:
|
This scaffold was within 10 feet of the overhead powerline with 300 volts to 50KV.
|
Description:
|
Hazard: Unguarded scaffolding.
|
|
|
|
Standard:
|
1926.451(f)(6)
|
Standard:
|
1926.451(c)(2)
|
|
|
|
Abatement:
|
The scaffold should not be erected, dismantlled, used or altered near energized powerlines.
|
Abatement:
|
Supported scaffold poles, legs, posts, frames, and uprights did not bear on base plates and mud sills or adequate firm foundation.
|
|
|